AWG sizes come from North America; most other countries use the metric sizes of IEC 60228. The two series do not line up, so every conversion has to pick a side. This chart gives the exact cross-section of each AWG size and the next IEC size up.
Updated 12 November 2026
AWG to mm²
| AWG | Diameter (solid), mm | Cross-section, mm² | Next IEC size up, mm² |
|---|---|---|---|
| 24 | 0.51 | 0.205 | 0.5 |
| 23 | 0.57 | 0.258 | 0.5 |
| 22 | 0.64 | 0.326 | 0.5 |
| 21 | 0.72 | 0.410 | 0.5 |
| 20 | 0.81 | 0.518 | 0.75 |
| 19 | 0.91 | 0.653 | 0.75 |
| 18 | 1.02 | 0.823 | 1 |
| 17 | 1.15 | 1.04 | 1.5 |
| 16 | 1.29 | 1.31 | 1.5 |
| 15 | 1.45 | 1.65 | 2.5 |
| 14 | 1.63 | 2.08 | 2.5 |
| 13 | 1.83 | 2.62 | 4 |
| 12 | 2.05 | 3.31 | 4 |
| 11 | 2.31 | 4.17 | 6 |
| 10 | 2.59 | 5.26 | 6 |
| 9 | 2.91 | 6.63 | 10 |
| 8 | 3.26 | 8.37 | 10 |
| 7 | 3.67 | 10.5 | 16 |
| 6 | 4.11 | 13.3 | 16 |
| 5 | 4.62 | 16.8 | 25 |
| 4 | 5.19 | 21.2 | 25 |
| 3 | 5.83 | 26.7 | 35 |
| 2 | 6.54 | 33.6 | 35 |
| 1 | 7.35 | 42.4 | 50 |
| 1/0 | 8.25 | 53.5 | 70 |
| 2/0 | 9.27 | 67.4 | 70 |
| 3/0 | 10.40 | 85.0 | 95 |
| 4/0 | 11.68 | 107 | 120 |
Diameters and areas follow the AWG formula of ASTM B258. Stranded wire of the same AWG has about the same copper area.
Larger sizes in kcmil
Above 4/0, North American sizes are given in thousands of circular mils: kcmil, formerly MCM. One kcmil is 0.5067 mm².
| kcmil | Cross-section, mm² | Next IEC size up, mm² |
|---|---|---|
| 250 | 127 | 150 |
| 300 | 152 | 185 |
| 350 | 177 | 185 |
| 400 | 203 | 240 |
| 500 | 253 | 300 |
| 600 | 304 | 400 |
| 750 | 380 | 400 |
mm² to AWG
| IEC size, mm² | Smallest common AWG or kcmil size that is not smaller | Its cross-section, mm² |
|---|---|---|
| 0.5 | 20 AWG | 0.518 |
| 0.75 | 18 AWG | 0.823 |
| 1 | 16 AWG | 1.31 |
| 1.5 | 14 AWG | 2.08 |
| 2.5 | 12 AWG | 3.31 |
| 4 | 10 AWG | 5.26 |
| 6 | 8 AWG | 8.37 |
| 10 | 6 AWG | 13.3 |
| 16 | 4 AWG | 21.2 |
| 25 | 3 AWG | 26.7 |
| 35 | 1 AWG | 42.4 |
| 50 | 1/0 AWG | 53.5 |
| 70 | 3/0 AWG | 85.0 |
| 95 | 4/0 AWG | 107 |
| 120 | 250 kcmil | 127 |
| 150 | 300 kcmil | 152 |
| 185 | 400 kcmil | 203 |
| 240 | 500 kcmil | 253 |
Building wire is rarely stocked in 17, 15, 13, 11, 9, 7 or 5 AWG, so this table skips those sizes.
Why the two series do not match
An AWG size is defined by the diameter of a solid wire, so its area is exact. An IEC 60228 size is nominal: a conductor passes if its resistance is at or below the limit for that size. A 2.5 mm² class 1 or class 2 copper conductor, for example, may have at most 7.41 Ω/km at 20 °C.
So never swap to a smaller size. 14 AWG is often listed as the equivalent of 2.5 mm², but it has only 2.08 mm² of copper, about 17% less. The other way round, 2.5 mm² can replace 14 AWG as far as cross-section goes.
Cross-section is only the first check. The current rating, the voltage drop over the run and the insulation rating must also meet the local wiring rules. US THHN wire, for instance, is rated 600 V, while IEC 60227 building wire is rated 450/750 V.
Cable standards and cross-referenceFAQ
What is 12 AWG in mm²?
12 AWG is 3.31 mm². The next IEC size up is 4 mm².
What is 10 AWG in mm²?
10 AWG is 5.26 mm². The next IEC size up is 6 mm².
What is 2.5 mm² in AWG?
2.5 mm² lies between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²). If you need a size that is not smaller, use 12 AWG.
Is 1.5 mm² the same as 16 AWG?
No. 16 AWG is 1.31 mm², about 13% less than 1.5 mm². The next common AWG size that is not smaller is 14 AWG, at 2.08 mm².